UI - Skripsi Membership :: Kembali

UI - Skripsi Membership :: Kembali

Pemilihan unit daur ulang efluen instalasi pengolahan air limbah di pembangkit listrik tenaga uap Muara Karang dengan metode analytical hierarchy process = The selection of recycling unit waste water treatment plant effluent in Muara Karang steam power plant with analytical hierarchy process method / Sutan Hamda R.

Sutan Hamda R; Setyo Sarwanto Moersidik, supervisor; Cindy R. Priadi, supervisor; ; Nyoman Suwartha, examiner ([Publisher not identified] , 2014)

 Abstrak

ABSTRAK
Kebutuhan air bersih untuk Pembangkit Listrik Tenaga Uap (PLTU) Muara
Karang cukup besar, sehingga diperlukan daur ulang untuk membantu mengatasi
kebutuhan air. Debit air yang didaur ulang sebesar 285 m3/hari. Tujuan penelitian
ini adalah untuk mendapatkan hasil efluen Instalasi Pengolahan Air Limbah
(IPAL) PLTU sehingga didapatkan perencanaan daur ulang yang sesuai. Daur
ulang tersebut digunakan untuk memenuhi kebutuhan air servis, hidran, dan
cadangan air pada PLTU Muara Karang. Hasil uji laboratorium efluen IPAL
PLTU Muara Karang yang tidak memenuhi baku mutu kelas II PP No. 82 Tahun
2001, yaitu TSS sebesar 67,5 ppm, BOD sebesar 4,76 ppm, dan COD sebesar 82,6
ppm sehingga diperlukan proses daur ulang untuk memenuhi kualitas air yang
sesuai dengan baku mutu. Terdapat tiga unit daur ulang, yaitu reverse osmosis,
ultrafiltrasi, dan mikrofiltrasi . Pemilihan unit daur ulang dari ketiga unit tersebut
ditentukan dengan metode Analytical Hierarchy Process (AHP) dengan kriteria
pemilihan berupa teknologi, ekonomi, dan lingkungan serta subkriteria
kemudahan operasional, keandalan proses, biaya konstruksi, biaya operasional
dan pemeliharaan, serta recovery product. Hasil pemilihan dengan metode AHP
menunjukkan unit daur ulang mikrofiltrasi merupakan unit yang tepat untuk
memenuhi kebutuhan air servis, hidran, dan cadangan dengan total skor tertinggi.

ABSTRACT
Clean water needs of Steam Power Plant Muara Karang is large enough so water
recycle is needed to help fulfill water needs. The discharge is 285 m3/day. The
purpose of the study is to obtain the results of waste water treatment plant effluent
to find the appropriate recycling plan. The recycled water is used to meet the
needs of services, hydrants, and water reserves in Muara Karang power plant.
Laboratory test results WWTP effluent Steam Power Plant Muara Karang that
does not meet the quality standard of Grade II PP No. 82 Tahun 2001, which is
amount 67,5 ppm TSS, BOD at 4,76 ppm and at 82,6 ppm COD so recycling is
needed. Selection of three recycling units selected from the reverse osmosis,
ultrafiltration, and microfiltration were conducted with Hierarchy Analytical
Process (AHP) with the selection criteria in the form of technology, economy, and
environment and then with sub-criteria of operational convenience, reliability
process, the cost of construction, operation and maintenance costs, and recovery
product . The results of the election showed AHP recycling microfiltration unit is
the right unit to meet the needs of water services, hydrants, and backup with the
highest total score.

 File Digital: 1

Shelf
 S54595-Sutan Hamda R.pdf :: Unduh

LOGIN required

 Metadata

Jenis Koleksi : UI - Skripsi Membership
No. Panggil : S54595
Entri utama-Nama orang :
Entri tambahan-Nama orang :
Entri tambahan-Nama badan :
Program Studi :
Subjek :
Penerbitan : [Place of publication not identified]: [Publisher not identified], 2014
Bahasa : ind
Sumber Pengatalogan : LibUI ind rda
Tipe Konten : text
Tipe Media : unmediated ; computer
Tipe Carrier : volume ; online source
Deskripsi Fisik : xvi, 83 pages : illustration ; 30 cm + appendix
Naskah Ringkas :
Lembaga Pemilik : Universitas Indonesia
Lokasi : Perpustakaan UI, Lantai 3
  • Ketersediaan
  • Ulasan
  • Sampul
No. Panggil No. Barkod Ketersediaan
S54595 TERSEDIA
Ulasan:
Tidak ada ulasan pada koleksi ini: 20368325
Cover