[Tata kelola udara atau sering disebut Heating, Ventilation and Air
Conditioning (HVAC) pada perusahaan farmasi mengkonsumsi energi listrik
sekitar 30% dari konsumsi listrik keseluruhan. Modifikasi teknologi pendingin
dengan alternatif teknologi Variable Speed Drive (VSD), Thermal Energy Storage
(TES) dan penggabungan keduanya menurunkan konsumsi energi listrik masing –
masing sebesar 10%, 30% dan 36%. Penggabungan dua teknologi VSD dan TES
menunjukkan nilai penurunan konsumsi energi listrik paling besar. Dan hasil
analisis keekonomian menunjukan hal yang sama bahwa penggabungan alternatif
VSD dan TES layak untuk dipilih. Hasil analisis aliran kas dan incremental
investment analysis menunjukan penggabungan teknologi VSD dan TES lebih
unggul dibanding alternatif yang lain dengan nilai NPV sebesar $79.185,00 dan
IRR sebesar 80.1%, pada jangka umur pakai 14 tahun. Tingkat kemungkinan
mendapatkan NPV > 0 sebesar 98,5% dan IRR > MARR sebesar 99.5%.;HVAC (Heating, Ventilation and Air Conditioning) on pharmaceutical
companies to consume electric energy about 30% of overall electricity
consumption. Modification of cooling technology with alternative technologies
VSD (Variable Speed Drive), (Thermal Energy Storage) and the incorporation of
both lowering the electrical energy consumption of each 10%, 30% and 36%.
Merging two VSD technology and TES showed a decrease in the value of electric
energy consumption at most. And the results of the economic analysis indicates
that the same thing that the incorporation of VSD and TES alternate eligible to be
selected. Results of the analysis of cash flow and incremental investment analysis
showed the incorporation of VSD and TES technology is superior to other
alternatives to the NPV of $ 79,185.00 and an IRR of 80.1%, in the period of
useful life of 14 years. The rate is likely to get NPV> 0 by 98.5% and IRR> MARR
of 99.5%., HVAC (Heating, Ventilation and Air Conditioning) on pharmaceutical
companies to consume electric energy about 30% of overall electricity
consumption. Modification of cooling technology with alternative technologies
VSD (Variable Speed Drive), (Thermal Energy Storage) and the incorporation of
both lowering the electrical energy consumption of each 10%, 30% and 36%.
Merging two VSD technology and TES showed a decrease in the value of electric
energy consumption at most. And the results of the economic analysis indicates
that the same thing that the incorporation of VSD and TES alternate eligible to be
selected. Results of the analysis of cash flow and incremental investment analysis
showed the incorporation of VSD and TES technology is superior to other
alternatives to the NPV of $ 79,185.00 and an IRR of 80.1%, in the period of
useful life of 14 years. The rate is likely to get NPV> 0 by 98.5% and IRR> MARR
of 99.5%.]