UI - Skripsi Membership :: Kembali

UI - Skripsi Membership :: Kembali

Studi kasus pengaruh variasi sudut fasa tegangan terhadap karakteristik nilai arus inrush pada energisasi transformator = A case study of the influence of switching angle variation to the characteristics of inrush current when energizing transformer

Sang Putu Sanat Kumara; I Made Ardita Y., supervisor; Chairul Hudaya, examiner; Agus R. Utomo, examiner ([Publisher not identified] , 2017)

 Abstrak

ABSTRAK
Transformator merupakan salah satu komponen yang memegang peranan
penting dalam sistem tenaga listrik. Sebagai sebuah komponen, transformator
memiliki spesifikasi tertentu yang telah ditentukan dari pabrik pembuatnya. Hal ini
dimaksudkan agar transformator tetap dapat beroperasi pada kondisi yang optial
dan terhindar dari resiko kerusakan yang mungkin saja terjadi. Salah satu penyebab
kerusakan pada transformator adalah terjadinya arus inrush pada saat proses
energisasi. Seringkali pada proses energisasi, arus inrush yang muncul bernilai
sangat besar, bahkan nilai dari arus inrush ini dapat mencapai 10 kali lipat dari arus
normal atau tunak.
Besar nilai dari arus inrush ini dipengaruhi oleh beberapa faktor dan salah
satunya adalah sudut fasa tegangan pada saat dilakukannya energisasi pada
transformator. Sudut fasa tegangan ini menentukan karakteristik nilai arus inrush
dimana sudut fasa tegangan pada titik nol akan memberikan nilai arus inrush yang
tinggi dan sudut fasa tegangan pada titik puncak tegangan akan memberikan nilai
arus inrush yang rendah. Pemilihan sudut fasa menjadi perhatian yang penting
dalam proses energisasi karena didalam proses energisasi tersebut diinginkan nilai
arus inrush yang serendah mungkin. Sehingga kerugian atau efek buruk yang
diakibatkan oleh arus inrush dapat diminimalisir.

ABSTRACT
Transformer is an important component of an electrical power system. As a
component, transformer has certain specifications that have been determined from
its manufacturer. This is meant so that the transformer can be operating at the
optimal condition and be avoided from any damages. One thing which can cause
damage to the transformer is the inrush current. An inrush current with very high
magnitude appears when the transformer is energized at its primary side. By
oftentimes at the energization process, the magnitude of inrush current can reach
ten times or more than the magnitude of steady-state current.
The magnitude of inrush current depends on several factors and one of them
is the voltage phase angle or shortly named as the switching angle. The switching
angle determines the characteristics of inrush current magnitudes. The switching
angle where the voltage source be at the zero voltage point results in high magnitude
of inrush current, meanwhile the switching angle where the voltage source be at its
positive or negative peak results in low magnitude of inrush current. The selection
of appropriate switching angle becomes an important consideration when
energizing a transformer, because at the energization process it is desired to get the
minimum value of inrush current. So that, the worst effects which are caused by the
existence of the inrush current can be minimalized.

 File Digital: 1

Shelf
 S66098-Sang Putu Sanat Kumara.pdf :: Unduh

LOGIN required

 Metadata

Jenis Koleksi : UI - Skripsi Membership
No. Panggil : S66098
Entri utama-Nama orang :
Entri tambahan-Nama orang :
Entri tambahan-Nama badan :
Program Studi :
Subjek :
Penerbitan : [Place of publication not identified]: [Publisher not identified], 2017
Bahasa : ind
Sumber Pengatalogan : LibUI ind rda
Tipe Konten : text
Tipe Media : unmediated ; computer
Tipe Carrier : volume ; online resource
Deskripsi Fisik : xv, 81 pages : illustration ; 30 cm + appendix
Naskah Ringkas :
Lembaga Pemilik : Universitas Indonesia
Lokasi : Perpustakaan UI, Lantai 3
  • Ketersediaan
  • Ulasan
  • Sampul
No. Panggil No. Barkod Ketersediaan
S66098 14-17-305080914 TERSEDIA
Ulasan:
Tidak ada ulasan pada koleksi ini: 20444611
Cover