Analisa koefisien perpindahan kalor eksperimen untuk aliran evaporasi dua fasa pada kanal mini horizontal dengan refrigeran R22 = Analysis of experimental two-phase flow boiling heat transfer coefficient in horizontal minichannel with refrigerant R-22

Sambas Prasetya; Agus Sunjarianto Pamitran, examiner; Engkos Achmad Kosasih, examiner; Nasruddin, examiner; Ardiyansyah, examiner (Fakultas Teknik Universitas Indonesia, 2011)

 Abstrak

ABSTRAK
Skripsi ini membahas mengenai koefisien perpindahan kalor aliran evaporasi dua
fasa refrigrant R-22 pada kanal mini horizontal. Dimana flux kalor yang diberikan
pada test section besarnya dapat divariasikan mulai dari 5 kW/m2 s/d 15 kW/m2.
Untuk bagian test section terbuat dari pipa stainless steel dengan diameter dalam 3
mm, diameter luar 5 mm dan panjang 1000 mm yang diberikan flux kalor yang
seragam disepanjang pipa tersebut dengan mengalirkan arus listirk dan
memberikan insulasi pada bagian luar test section untuk meminimalisasi kalor
yang terbuang kelingkungan. Begitu pula dengan t emperatur saturasi divariasikan
-5°C,0°C,5°C dan 10°C. Untuk memperoleh besarnya nilai koefisien perpindahan
kalor aliran dua fasa dilakukan dengan melakukan percobaan dan
membandingkan hasilnya dengan menggunakan simulasi perhitungan dengan
program MATLAB, dimana nantinya diperoleh nilai koefisien perpindahan kalor
hasil pengukuran, perhitungan dengan menggunakan korelasi Chen. Pada aliran
dua fasa, kualitas massa uap memiliki pengaruh yang tidak signifikan pada
koefisien perpindahan kalor pada daerah kualitas rendah akan tetapi memiliki
pengaruh yang signifikan pada daerah kualitas yang tinggi. Kenaikan koefisien
perpindahan kalor dipengaruhi oleh heat flux yang diberikan. Dimana semakin
besar heat flux yang diberikan maka koef isien perpindahan kalornya akan semakin
besar pula.

ABSTRACT
This minithesis discuss about heat transfer coefficient of evaporation two phase
flow in horizontal minichannel with refrigerant R -22. Heat flux given to the test
section can be varied from 5 kW/m2 up to 15 kW/m2. The test section was made of
stainless steel tuve with inner diameter of 3 mm, outer diameter of 5 mm and
length 1000 mm which was heated uniformly along the tuve by applying an
electric current and outside of the test section was insulated well to prevent heat
loss to surrounding environment. And also with saturation temperature from
0°C,5°C dan 10°C. To obtain two phase flow heat transfer coefficients were used
simulation of calculation using MATLAB, which later, the value of heat transfer
coefficient obtained were measurent and calculation were used Chen correlation.
In Two-phase flow, mass vapour quality had insignificant effect in the lower
quality región, but had significant effect in the higher quality región to heat
transfer coefficient.. Increasing of heat transfer coefficient ere effected by
addition of heat flux given in certain value. Higher heat flux given will result in
higher value of heat transfer coefficient..

 File Digital: 1

Shelf
 S1789-Analisis koefisien.pdf :: Unduh

 Metadata

No. Panggil : S1789
Entri utama-Nama orang :
Entri tambahan-Nama orang :
Entri tambahan-Nama badan :
Subjek :
Penerbitan : [Place of publication not identified]: Fakultas Teknik Universitas Indonesia, 2011
Program Studi :
Bahasa : ind
Sumber Pengatalogan : LibUI ind rda
Tipe Konten : text
Tipe Media : unmediated ; computer
Tipe Carrier : volume ; online resources
Deskripsi Fisik : xiii, 86 pages ; 30 cm
Naskah Ringkas :
Lembaga Pemilik : Universitas Indonesia
Lokasi : Perpustakaan UI, Lantai 3
  • Ketersediaan
  • Ulasan
No. Panggil No. Barkod Ketersediaan
S1789 TERSEDIA
Ulasan:
Tidak ada ulasan pada koleksi ini: 20295510