Konverter AC-DC tiga-pasa terkendali terhadap total harmonic distortion (THD) pada beban induktif berbasis Lab VIEW / Kusnadi

Kusnadi; Prawito Prajitno, supervisor; Sastra Kusuma Wijaya, examiner; Silva, B.E.F. da, examiner; Ahmad Tossin Alamsyah, examiner (Universitas Indonesia, 2012)

 Abstrak

Aplikasi beban non linier sangat luas digunakan di industri rumah tangga, gedung perkantoran dan pabrik seperti konverter daya untuk pengendalian kecepatan motor ac/dc, un-interruptible power supplies (UPS) lampufluorescent yang menggunakan ballas elektronik. Penggunaan konverter ac-dc elektronika akan menarik arus terdistorsi yang mengandung komponen harmonisa dan secara keseluruhan akan menyebabkan faktor daya sistem menjadi berkurang. Arus yang terdistorsi akan mengandung THD%(Total Harmonic Distortion). Dalam pengoperasian konverter ac-dc tiga fasa terkendali, pengaturan sudut penyalaan merupakan hal yang perlu diperhatikan. Pemberian sudut penyalaan yang tidak tepat dapat menyebabkan konverter ac-dc tidak bekerja secara optimal.
Pada penelitian ini, suatu metoda baru dipresentasikan untuk mengukur THD% secara otomatis pada sisi masukan jala-jala konverter ac-dc tiga fasa terkendali sebagai fungsi dari sudut penyalaan pada beban induktif berbasis LAB-VIEW 8,5 dan NI-DQ 6008. Ekperimen dilakukan dilaboratorium dengan cara mengevaluasi nilai THD% dan mencari operasi kerja sudut penyalaan sebagai fungsi dari %THD pada sisi masukan jala-jala konverter ac-dc tiga fasa terkendali untuk beban induktif dengan menggunakan software LabVIEW 8,5 dan Hardware NIDQ 6008.
Hasil ekperimen menghasilkan nilai operasi kerja converter ac-dc :Pada beban L1=0,25H Nilai 31%≤ THD≤35% dan 52,2≤ (α0)≤58,09 ,dengan presentasi kesalahan ≤0,2%. Untuk THD<31% akan mendapatkan nilai %E >5%, sedangkan untuk THD%> 35% 𝑎𝑘𝑎𝑛 𝑚𝑒𝑛𝑑𝑎𝑝𝑎𝑡𝑘𝑎𝑛 %𝐸>4%. Pada beban L2=0,56H. Nilai 31%≤THD≤36%dan (α0) =54 untuk (α0) dari THD 31% -36% ,sudut penyalaan akan konstan sebesar =54 derajat dengan persentasi kesalahan≤ 3%.

Application of non linear loads are widely used in household industries, office buildings and factories such as power converters for motor speed control of ac/dc, uninterruptible power supplies (UPS) lamp fluorescent using electronic Ballas. Ac-dc converters use of electronics will draw distorted current containing harmonic components and will cause the overall system power factor is reduced. Distorted currents will contain THD% (Total Harmonic Distortion). In the operation of ac-dc converter controlled three-phase, setting the ignition point is worth noting. Giving improper ignition angle can cause the ac-dc converters do not work optimally.
In this study, presented a new method to measure the THD% automatically on the input side of the net ac-dc converter controlled three-phase as a function of ignition angle based on an inductive load LAB-VIEW 8.5 and NI-DQ 6008. Laboratory experiments conducted by evaluating the value of THD% and looking for work operations ignition angle as a function of% THD on the input side of the net ac-dc converter is controlled to a three-phase inductive load using LabVIEW 8.5 software and Hardware NI-DQ 6008.
Experimental results of the operation value of work ac-dc converter: The load L1 = 0.25 H. Value of 31% ≤ THD ≤ 35% and ≤ 52.2 (α0) ≤ 58.09, with a presentation error ≤ 0.2%. For THD <31% will get the value of% E> 5%, while for THD%> 35% will get a% E> 4%. On load L2 = 0.56 H.Nilai THD ≤ 31% ≤ 36% and (α0) = 54 with a percentage error ≤ 3%.

 File Digital: 1

Shelf
 T30913-Konventer AC-DC.pdf :: Unduh

LOGIN required

 Metadata

No. Panggil : T30913
Entri utama-Nama orang :
Entri tambahan-Nama orang :
Subjek :
Penerbitan : [Place of publication not identified]: Universitas Indonesia, 2012
Program Studi :
Bahasa : ind
Sumber Pengatalogan : LibUI ind rda
Tipe Konten : text
Tipe Media : unmediated ; computer
Tipe Carrier : volume ; online resource
Deskripsi Fisik : xiv, 49 pages :illustration ; 30 cm
Naskah Ringkas :
Lembaga Pemilik : Universitas Indonesia
Lokasi : Perpustakaan UI, Lantai 3
  • Ketersediaan
  • Ulasan
No. Panggil No. Barkod Ketersediaan
T30913 TERSEDIA
Ulasan:
Tidak ada ulasan pada koleksi ini: 20314576