Perpindahan kalor, penurunan tekanan dan pola aliran dalam flow boiling duafase dengan R-290 dan R-22 pada pipa berdiameter 7.6 mm = Two phase flow boiling heat transfer pressure drop and flow pattern of R-22 and R-290 in 7.6 mm circular tube diameter / Helmi Dadang Ardiansyah

Helmi Dadang Ardiansyah; Agus Sunjarianto Pamitran, supervisor (Fakultas Teknik Universitas Indonesia, 2013)

 Abstrak

ABSTRAK
Karaketeristik didih alir R-290 menjadi hal yang penting untuk diteliti setelah R-22 mulai dibatasi, karakteristik ini pertukaran kalor, penurunan tekanan, dan pola aliran yang diharapkan dapat menggantikan posisi R-22 dengan R-290 sebagai media pendingin berbahan refrijeran alami. Dalam percobaan aliran didih R-290 dan R-22 sebagai pembanding dilakukan dalam pipa konvensional yang masih banyak digunakan dalam industri dan sistem pendingin rumah tangga. Variasi fluks kalor dari 5.09 kW/m2 sampai 19.03 kW/m2, fluks massa dari 339.74 kg/m2.s sampai 751.74 kg/m2.s dan temperatur saturasi 5.59 oC sampai 18.12 oC untuk R-22 dan sedangkan R-290 dari 114.91 kg/m2.s sampai 637.63 kg/m2.s dan temperatur saturasi dari 4.77 oC sampai 16.45 oC dengan fluks kalor yang sama dengan R-22. Hasil yang didapat adalah penurunan tekanan dipengaruhi oleh fluks kalor, fluks massa dan temperatur saturasi serta R-290 mempunyai penurunan tekanan lebih rendah dibanding R-22. Sedangkan untuk perpindahan kalor, variasi fluks massa menunjukkan tidak ada perubahan baik untuk R-22 dan R-290. Persamaan prediksi Lokhart-Martinelli (1949) hasil yang paling baik untuk penurunan tekanan eksperimen. Kandlikar (1990) mempunyai prediksi paling baik untuk R-22. Untuk pola aliran dibandingkan antara observasi langsung dengan prediksi pola aliran dari Wojtan et al (2005) dan Wang et al (1997).

ABSTRACT
The characteristic of flow boiling R-290 is very important immediately to observeinstead of R-22 was limited, there are such as heat transfer, pressure drop flow boiling and flow pattern that are hoped can change R-22 into R-290 as natular refrigeration. The experiment of flow boiling R-290 and R-22 as comparable was conducted in conventional channel which was used industry. Variation of heat flux was strarted from 5.09 kW/m2to 19.03 kW/m2, Mass flux was 339.74 kg/m2.s to 751.74 kg/m2.s and saturation temperature was 5.59 oC to 18.12 oC for R-22 and R-290 was 114.91 kg/m2.s to 637.63 kg/m2.s and saturation temperatur was4.77 oC to 16.45 oC within heat flux sas big as R-22. The result given interesting value to deeply observation later. Pressure drop was depended by heat flux, mass flux and saturation temperatur and The experiment admitted that R-290 has pressure drop lower than R-22. Mass flux lower slightly changed on heat transfer coefficient for R-22 and R-290. Lokhart-Martinelli (1949) given good prediction on pressure drop data experiment and Kandlikar (1990) has smaller error for prediction of heat transfer flow boiling. This paper presented comparation of flow pattern form Wojtan et al (2005) and Wang et al (1997).

 File Digital: 1

Shelf
 T35450-Helmi Dadang.pdf :: Unduh

LOGIN required

 Metadata

No. Panggil : T35450
Entri utama-Nama orang :
Entri tambahan-Nama orang :
Entri tambahan-Nama badan :
Subjek :
Penerbitan : [Place of publication not identified]: Fakultas Teknik Universitas Indonesia, 2013
Program Studi :
Bahasa : ind
Sumber Pengatalogan : LibUI ind rda
Tipe Konten : text
Tipe Media : unmediated ; computer
Tipe Carrier : volume ; online resource
Deskripsi Fisik : xxiv, 167 pages ; 28 cm + appendix
Naskah Ringkas :
Lembaga Pemilik : Universitas Indonesia
Lokasi : Perpustakaan UI, Lantai 3
  • Ketersediaan
  • Ulasan
No. Panggil No. Barkod Ketersediaan
T35450 TERSEDIA
Ulasan:
Tidak ada ulasan pada koleksi ini: 20349021