Analisis pengaruh kehilangan suplai daya dan pelepasan konduktor transmisi terhadap kestabilan tegangan sistem 500 kv berdasarkan kurva pv = Voltage stability analysis of 500 kv system due to power supply and transmission conductor loss using pv curve method

Ade Rustiawati Wijaya; Agus R. Utomo, supervisor; I Made Ardita Y., examiner; Faiz Husnayain, examiner (Fakultas Teknik Universitas Indonesia, 2015)

 Abstrak

Kestabilan tegangan merupakan salah satu syarat sistem operasi tenaga listrik. Tegangan pada sistem tenaga listrik akan mengalami collapse seiring dengan kenaikan beban yang terus menerus hingga mencapai batas maksimumnya. Selain itu terlepasnya unit-unit pembangkit dan sirkit penghantar juga merupakan salah satu penyebab jatuhnya tegangan.
Dalam studi kasus ini, tegangan krititis pada Subsistem Bekasi Cibatu dan Kembangan akan dianalisis dengan menggunakan metode kurva PV. Kurva ini menjelaskan hubungan antara daya aktif dan tegangan pada suatu bus. Dengan menaikkan beban, maka nilai tegangan kritis pada pembebanan maksimum dapat diperoleh.
Hasil penelitian menunjukkan bahwa susbistem yang diterapkan skenario lepas pembangkit Unit 8 PLTU Suralaya memiliki tegangan kritis terendah sekaligus penurunan tegangan kritis terbesar yaitu subsistem Cibatu dengan tegangan kritis sebesar 423.087 kV atau mengalami penurunan sebesar 5.192 % dari tegangan kritis kondisi normalnya.

Voltage stability is one of requirements among operation of electrical power system. Voltage on electrical power system will collapse along with continuously rising load until its maximum limit and due to lose of generator unit and conductor circuit.
In this study case, critical voltage at these Subsystem Bekasi Cibatu and Kembangan will be analyzed using PV curve method. The curve explains relationship between active power and voltage on a load bus. Critical voltage value on maximum loading can be yielded when load is increased.
This research resulted that application of lose scenario of PLTU Suralaya Unit 8 has the biggest impact of critical voltage drop at Cibatu subsystem. Critical voltage of Cibatu subsystem is 423.087 kV or its critical voltage decrease to 5.192 % from its critical voltage at normal condition.

 File Digital: 1

Shelf
 S58702-Ade Rustiawati Wijaya.pdf :: Unduh

LOGIN required

 Metadata

No. Panggil : S58702
Entri utama-Nama orang :
Entri tambahan-Nama orang :
Entri tambahan-Nama badan :
Subjek :
Penerbitan : Depok: Fakultas Teknik Universitas Indonesia, 2015
Program Studi :
Bahasa : ind
Sumber Pengatalogan : LibUI ind rda
Tipe Konten : text
Tipe Media : unmediated ; computer
Tipe Carrier : volume ; online resource
Deskripsi Fisik : xii, 65 pages : illustration ; 30 cm + appendix
Naskah Ringkas :
Lembaga Pemilik : Universitas Indonesia
Lokasi : Perpustakaan UI, Lantai 3
  • Ketersediaan
  • Ulasan
No. Panggil No. Barkod Ketersediaan
S58702 14-21-114972603 TERSEDIA
Ulasan:
Tidak ada ulasan pada koleksi ini: 20402259