:: UI - Skripsi Membership :: Kembali

UI - Skripsi Membership :: Kembali

Variasi tuning dan quality factor pada perancangan single tuned passive filter untuk optimasi reduksi distorsi harmonik = Variation of tuning and quality factor in single tuned passive filter design to optimize the reduction of harmonic distortion

Fauziah Aini; Agus R. Utomo, supervisor; I Made Ardita Y., examiner; Faiz Husnayain, examiner (Fakultas Teknik Universitas Indonesia, 2015)

 Abstrak

Skripsi ini membahas tentang upaya reduksi harmonik pada sistem tenaga listrik yang memiliki beban non-linier variable frequency drives dengan menggunakan single-tuned passive filter. Variasi tuning dan quality factor pada perancangan filter dilakukan untuk mendapatkan nilai reduksi yang optimal dan memenuhi standar IEEE 519-1992. Variasi tuning factor yang dilakukan adalah ± 0.5 dari orde harmonik dominan dan variasi quality factor adalah 1 hingga 80. Dari hasil simulasi menggunakan ETAP 7.0.0, nilai reduksi harmonik optimal didapatkan dengan pemasangan dua buah single-tuned passive filter dengan tuning factor 5.1 dan 11.1 dan quality factor 60 hingga 80. Besarnya reduksi harmonik arus adalah 16.11% dan besarnya reduksi harmonik tegangan adalah 8.11%, dimana nilai individual harmonic distortion dan total harmonic distortion telah memenuhi standar. Tingkat pembebanan pada transformator penyuplai juga berhasil diturunkan dari 81% menjadi 69.6%.

This focus of study is about the reduction of harmonic distortion in power system supplied non-linear loads variable frequency drives using single-tuned passive filter. Variation of tuning and quality factor has been done to optimize harmonic reduction value to meet IEEE 519-1992 requirement. Variation of tuning factor is ± 0.5 around its dominant harmonic order and variation of quality factor is 1 up to 80. Simulation using ETAP 7.0.0 results optimum reduction of harmonic distortion is achieved by using 2 single-tuned passive filters with tuning factor 5.1 and 11, and quality factor 60 up to 80. Current harmonic distortion has been reduced 16.11% and voltage harmonic distortion has been reduced 8.11%, where individual harmonic distortion and total harmonic distortion has met the requirement. Feeder transformer loading has been reduced from 81% to 69.6%.

 File Digital: 1

Shelf
 S58236-Fauziaha Aini.pdf :: Unduh

LOGIN required

 Metadata

No. Panggil : S58236
Entri utama-Nama orang :
Entri tambahan-Nama orang :
Entri tambahan-Nama badan :
Subjek :
Penerbitan : Depok: Fakultas Teknik Universitas Indonesia, 2015
Program Studi :
Bahasa : ind
Sumber Pengatalogan :
Tipe Konten : text
Tipe Media : unmediated ; computer
Tipe Carrier : volume ; online resource
Deskripsi Fisik : xii, 56 pages : illustration ; 30 cm + appendix
Naskah Ringkas :
Lembaga Pemilik : Universitas Indonesia
Lokasi : Perpustakaan UI, Lantai 3
  • Ketersediaan
  • Ulasan
No. Panggil No. Barkod Ketersediaan
S58236 14-20-152895750 TERSEDIA
Ulasan:
Tidak ada ulasan pada koleksi ini: 20402380