Evaluasi penerapan keselamatan kebakaran gedung menggunakan computerized fire safety evaluation system (CFSES) di Fakultas Kedokteran Universitas Indonesia tahun 2014

Dea Pisca Permaswhari; Fatma Lestari, supervisor; Mila Tejamaya, examiner; Pangaribuan, Adrianus, examiner (Fakultas Kesehatan Masyarakat Universitas Indonesia, 2015)

 Abstrak

Skripsi ini membahas evaluasi penerapan keselamatan kebakaran gedung dengan menggunakan perangkat lunak Computerized Fire Safety Evaluation System (CFSES) di Fakultas Kedokteran Universitas Indonesia yang berlokasi di Salemba, Jakarta Pusat. Evaluasi dilakukan berdasarkan kesesuaian 12 safety parameters dan persyaratan tambahan pada NFPA 101A: Alternate Approaches to Life Safety dengan standar NFPA 101: Life Safety Code. Disain studi penelitian adalah deskriptif dengan pendekatan semi kuantitatif. Sampel penelitian adalah Gedung Utama dan Gedung Departemen Kimia FKUI.
Hasil evaluasi Gedung Utama menunjukkan bahwa kontrol penyebaran api mendapatkan nilai -9 dari standar persyaratan minimum -4. Sistem jalan keluar mendapatkan nilai -12.5 dari standar 0. Sedangkan keselamatan kebakaran umum mendapatkan nilai -17 dari standar -4. Hasil evaluasi Gedung Departemen Kimia menunjukkan bahwa kontrol penyebaran api mendapatkan nilai -9,5 dari standar persyaratan minimum -4. Sistem jalan keluar mendapatkan nilai -5.5 dari standar 0. Sedangkan keselamatan kebakaran umum mendapatkan nilai -8 dari standar -4.
Hasil penelitian menyimpulkan bahwa penerapan keselamatan kebakaran di Gedung Fakultas kedokteran Universitas Indonesia belum memenuhi persyaratan keselamatan minimum pada NFPA 101: Life Safety Code.

This study discusses evaluation of the fire safety implementation of buildings using software Computerized Fire Safety Evaluation System (CFSES) at Faculty of Medicine, University of Indonesia, located in Salemba, Central Jakarta. The evaluation was done based on the suitability of 12 safety parameters and additional requirements in NFPA 101A: Alternate Approaches to Life Safety with standards NFPA 101: Life Safety Code. Design of this study is descriptive with a semi-quantitative approach. Samples are the Main Building and the Department of Chemistry Building, Faculty of Medicine.
Results of main building evaluation shows that the score of fire control is -9, score of egress is -12.5, and score of general fire safety is -17. Meanwhile, for chemistry building, the score for fire control is -9.5, score of egress is -5.5, and score of general fire safety is -8.
The study concluded that the fire safety implementation in the Faculty of Medicine University of Indonesia has not met the minimum safety requirements in NFPA 101: Life Safety Code.

 File Digital: 1

Shelf
 S58298-Dea Pisca Permaswhari.pdf :: Unduh

LOGIN required

 Metadata

No. Panggil : S58298
Entri utama-Nama orang :
Entri tambahan-Nama orang :
Subjek :
Penerbitan : Depok: Fakultas Kesehatan Masyarakat Universitas Indonesia, 2015
Program Studi :
Bahasa : ind
Sumber Pengatalogan :
Tipe Konten : text
Tipe Media : unmediated ; Computer (rdadontent)
Tipe Carrier : volume ; online resource
Deskripsi Fisik : xv, 124 pages : illustration ; 30 cm + appendix
Naskah Ringkas :
Lembaga Pemilik : Universitas Indonesia
Lokasi : Perpustakaan UI, Lantai 3
  • Ketersediaan
  • Ulasan
No. Panggil No. Barkod Ketersediaan
S58298 14-23-86671158 TERSEDIA
Ulasan:
Tidak ada ulasan pada koleksi ini: 20402513