Full Description

Cataloguing Source : LibUI eng rda
ISSN : 20869614
Magazine/Journal : International Journal of Technology
Volume : Vol. 9, No. 2, April 2018: Hal. 422-429
Content Type : text (rdacontent)
Media Type : unmediated (rdamedia)
Carrier Type : volume (rdacarrier)
Electronic Access : https://doi.org/10.14716/ijtech.v9i2.1150
Holding Company : Universitas Indonesia
Location : Perpustakaan UI, Lantai 4 R. Koleksi Jurnal
 
  •  Availability
  •  Digital Files: 0
  •  Review
  •  Cover
  •  Abstract
Call Number Barcode Number Availability
UI-IJTECH 9:2 (2018) 08-23-13029477 TERSEDIA
No review available for this collection: 9999920522112
 Abstract
This study was conduct to identify the effectiveness and heat recovery values of heat pipe heat exchangers (HPHEs) in heating ventilating air conditioning (HVAC) ducting systems. HPHEs are passive modules which provide the energy recovery function in HVAC systems. In this research the HPHE module consist of 42 heat pipe tubes equipped with 120 wavy fins on the evaporator and condenser sections. In this study the HPHE module was tested with a three-row configuration design, and at inlet airflow temperatures of 28, 30, 35, 40, and 45ºC. The velocity of inlet air also varied, at 1, 1.5, and 2 m/s. The results show that in the three-row configuration the inlet temperature decreased by a maximum of 10.3°C. This configuration also has an HPHE effectiveness value of between 47.9 and 54.4%. The highest effectiveness value (54.4%) was obtained at inlet air velocity and temperature of 1 m/s and 45ºC, respectively. The highest HPHE heat recovery value was 5,368 W at 2 m/s inlet air velocity, giving a 51.7% HPHE effectiveness rating. This HPHE system can be considered as saving energy for HVAC systems.