Deskripsi Lengkap

Sumber Pengatalogan : LibUI eng rda
ISSN : 20869614
Majalah/Jurnal : International Journal of Technology
Volume : Vol. 7, No. 7, December 2016: Hal. 1253-1259
Tipe Konten : text (rdacontent)
Tipe Media : unmediated (rdamedia)
Tipe Carrier : volume (rdacarrier)
Akses Elektronik : https://doi.org/10.14716/ijtech.v7i7.4654
Institusi Pemilik : Universitas Indonesia
Lokasi : Perpustakaan UI, Lantai 4 R. Koleksi Jurnal
 
  •  Ketersediaan
  •  File Digital: 0
  •  Ulasan
  •  Sampul
  •  Abstrak
No. Panggil No. Barkod Ketersediaan
UI-IJTECH 7:7 (2016) 08-23-00922604 TERSEDIA
Tidak ada ulasan pada koleksi ini: 9999920530901
 Abstrak
The objective of this research was to study the effects of highly moist inlet air conditions such as temperature, relative humidity, and frontal air velocity on the value of the Lewis number (Le) in the cooling and dehumidifying process of air. A finned tube cooling coil was tested under ranges of temperature, relative humidity and frontal velocity. It was found that the Lewis number (Le) varied within the range of 0.92?1.62 and that the increase in inlet air relative humidity tends to decrease the Lewis number (Le). Based on the experimental, a correlation for predicting the Lewis number (Le) was also established in this article. The correlation has the mean absolute error (MAE) of 3.04% and covers 98.07% of the data where a discrepancy within ± 10%.